Home » Store » IBM » IBM Misc » IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424

IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424

IBM #1051 battery assembly, a DC-UPS battery service module set for the DS8870 (2421, 2422, 2423, 2424).

Sourcing mission-critical hardware shouldn't mean gambling on auction sites or automated shopping carts. You get direct access to dedicated specialists who answer the phone, confirm exact compatibility, and deliver project-ready pricing built around your deployment timeline.

Home / Shop

IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424
IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424
IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424

Home / Shop

IBM #1051 Battery Assembly for DS8870 2421, 2422, 2423 and 2424

Model Number: IBM FC 1051
IBM #1051 battery assembly, a DC-UPS battery service module set for the DS8870 (2421, 2422, 2423, 2424).
Maximum quantity exceeded
Minimum purchase amount of 0 is required
Maximum purchase amount of 0 is allowed
Missing Inquiry Options
*Your Name:
*Your Email:
*Your Message:
Please send me a copy
0.000
Categories: IBM Misc
Manufacturer: IBM
Facebook
X
Email
LinkedIn
  • Description
  • Specifications

IBM feature #1051 is the battery assembly for the IBM System Storage DS8870, machine types 2421, 2422, 2423 and 2424, models 961 and 96E. It is the single-phase DC-UPS battery service module, applies to all models, and is a lead acid battery set.

Every DS8870 rack contains two DC-UPS units with integrated batteries, and each DC-UPS takes one or two battery service module sets depending on the configuration ordered. A model 961 or 96E without the extended power line disturbance option (#1055) takes one #1051 set per DC-UPS, and a model with #1055 takes two. The on-battery period is 4 seconds without #1055 and 50 seconds with it. If both DC-UPS units in a frame lose AC input, the units go on battery and the system starts a shutdown when AC is not restored.

Battery service module sets sit at UPS locations E1-E12 and E2-E12 in every system, with further sets at E1-E11 and E2-E11 and, in larger configurations, E1-E10 and E2-E10. Each set connects through a primary module with J20 power and J30 signal connectors and secondary modules with J21 power and J31 signal connectors. A separate feature code is not required for the DC-UPS itself.

Feature code#1051
DescriptionBattery assembly (single-phase DC-UPS battery service module)
SystemIBM System Storage DS8870
Machine types2421, 2422, 2423, 2424
Models961, 96E (all models)
Battery typeLead acid
Sets per DC-UPS1 without #1055, 2 with #1055
On-battery period4 seconds without #1055, 50 seconds with #1055
Set locationsE1-E12, E2-E12, E1-E11, E2-E11, E1-E10, E2-E10
Related feature#1055 extended power line disturbance