Home / Shop


- Description
- Specifications
Nine C19 receptacles sit on the front of feature #ECJJ, the High Function 9xC19 PDU plus, an intelligent, switched 200-240 V AC power distribution unit for 7014, 7953 and 7965 racks. Three C13 receptacles complete the receptacle set. The PDU mounts on the rear of the rack with the C19 receptacles within reach, and horizontal mounting uses 1U of rack space.
The unit measures the electrical power drawn by the devices plugged into it, reports usage by receptacle, and can switch an individual receptacle on or off remotely. Depending on country wiring standards it is single-phase or three-phase wye; with three-phase wye wiring the input is 380-415 V AC and the output is 220-240 V AC. Each PDU takes one PDU-to-wall power cord, ordered separately, and the cord sets the amperage at 16 A, 24 A, 32 A, 48 A or 63 A. Depending on the cord, the PDU supplies between 4.8 and 19.2 kVA.
The chassis is 42.5 mm high, 447.5 mm wide and 351 mm deep, with 25 mm of added clearance for the circuit breakers and 3 mm for the outlets. C19 models weigh 5.25 kg (11.6 lb). Six double-pole branch circuit breakers rated 20 A and derated to 16 A feed the outlets. Rated frequency is 50-60 Hz, humidity is 8-80% noncondensing, and room ambient temperature is 10-60 C (50-140 F).
| Feature code | #ECJJ |
| Description | High Function 9xC19 PDU plus |
| Rack types | 7014, 7953, 7965 |
| Function | Intelligent, switched, power monitoring |
| Receptacles | 9 IEC 320-C19 on the front plus 3 IEC 320-C13 |
| Input | 200-240 V AC, single-phase or three-phase wye (380-415 V input, 220-240 V output) |
| Amperage | 16 A, 24 A, 32 A, 48 A or 63 A, set by the power cord |
| Circuit breakers | Six double-pole, 20 A derated to 16 A |
| Size (H x W x D) | 42.5 x 447.5 x 351 mm |
| Weight | 5.25 kg (11.6 lb) |
| Frequency | 50-60 Hz |
| Mounting | Rear of rack, horizontal (1U) |
| Power cord | One PDU-to-wall cord per PDU, ordered separately |