For three-phase delta wiring, feature #ECJL is the High Function 9xC19 PDU plus 3-Phase: an intelligent, switched AC power distribution unit with nine C19 receptacles on the front panel, for 7014, 7953 and 7965 racks. It is rated 200-240 V AC, with 208 V three-phase service for countries on delta wiring, and three C13 receptacles accompany the nine C19 outlets.
Mounted on the rear of the rack, the PDU leaves its C19 receptacles within easy reach; two or more can be installed horizontally, and each horizontal PDU takes 1U. Power use is monitored by receptacle and each receptacle can be switched remotely. One PDU-to-wall power cord is required per PDU and is ordered separately. The cord rating is 24 A, 40 A or 48 A, and the PDU can supply between 4.8 and 19.2 kVA depending on the cord used.
Overall dimensions are 42.5 mm high by 447.5 mm wide by 351 mm deep, with 25 mm clearance at the circuit breakers and 3 mm at the outlets. A C19 model weighs 5.25 kg (11.6 lb). Six double-pole 20 A branch breakers, derated to 16 A, protect the outlets. The unit is rated for 50-60 Hz and 8-80% noncondensing humidity, with a room ambient range of 10-60 C (50-140 F).
| Feature code | #ECJL |
| Description | High Function 9xC19 PDU plus 3-Phase |
| Rack types | 7014, 7953, 7965 |
| Function | Intelligent, switched, power monitoring |
| Receptacles | 9 IEC 320-C19 on the front plus 3 IEC 320-C13 |
| Input | 200-240 V AC, three-phase, delta wired (208 V three-phase) |
| Amperage | 24 A, 40 A or 48 A, set by the power cord |
| Circuit breakers | Six double-pole, 20 A derated to 16 A |
| Size (H x W x D) | 42.5 x 447.5 x 351 mm |
| Weight | 5.25 kg (11.6 lb) |
| Frequency | 50-60 Hz |
| Mounting | Rear of rack, horizontal (1U) |
| Power cord | One PDU-to-wall cord per PDU, ordered separately |